• 60227 IEC 01 THW

    450/750 V 70°C SOLID AND STRANDED CONDUCTOR PVC INSULATED, SINGLE CORE


    Conductor   : Stranded annealed copper wire
    : Sizes 6 mm² up to 185 mm²
    Insulation : Polyvinyl chloride (PVC/C)
    Core identification : Single – cores  : Any color
       
    Classification : Maximum conductor temperature 70°C
    : Circuit voltage not exceeding 450/750 Volts
      450 Volts between Line-to-Earth
      750 Volts between Line-to-Line
    Testing voltage : 2,500 Volts
    Reference standard : TIS 11 Part 3-2553, Table 1
  • YK FD-0.6/1KV-CV

    0.6/1 kV 90 °C CROSS-LINKED POLYETHYLENE INSULATED PVC SHEATHED PVC SHEATHED FLAME RETARDANT SUPER SOFT POWER CABLE


    Conductor   : Non-compacted and compacted round annealed    copper
    : Single-core : Size 2.5 mm²  up to 240 mm²
    : Multi-core : Size 2.5 mm²  up to 70 mm²
     
    Insulation : Cross-linked Polyethylene (XLPE)
    Core identification Single-core : Natural (Translucent)
    2 Core : Blue and Brown
    3 Core : Brown, Black and Grey
    4 Core : Blue, Brown, Black and Grey
    Other colors are available on customer request
     
    Inner sheath : Black flame retardant polyvinyl chloride       (PVC/ST2)
    Outer sheath : Black polyvinyl chloride (PVC/ST4)
    Classification : Maximum conductor temperature 90°C
    : Circuit voltage not exceeding 1,200 Volts
      Rated voltage (U/U) 0.6/1 KV
      600 Volts between Line-to-Earth
      1,000 Volts between Line-to-Line
     
    Testing voltage : 3,500 Volts
    Reference standard : IEC 60502-1, IEC 60228, IEC 60332-1
    : IEC 60332-3-24 (Cat.C)