• 1.8/3 KV-CV

    1.8/3 (3.6) kV 90°C CROSS-LINKED POLYETHYLENE INSULATED AND PVC SHEATHED POWER CABLE


    Conductor   : Compact round stranded annealed copper,
    Single-core : Size 10 mm²  up to 400 mm²
    Multi-core : Size 10 mm²  up to 400 mm²
    Insulation : Cross-Linked polyethylene (XLPE)
    Core identification Single-core : Natural (Translucent)
    3 core : White, Red and Blue
    Shield : Copper tape
    Outer sheath : Black polyvinyl chloride (PVC/ST2)
    Classification : Maximum conductor temperature 90°C
    : Circuit voltage not exceeding 3,600 Volts
      Rated voltage (U0/U) 1.8/3 kV
      1,800 Volts between Line-to-Earth
      3,000 Volts between Line-to-Line
    Testing voltage : 6,500 Volts
    Reference standard : IEC 60502-1, IEC 60228, IEC 60332-1
  • 3.6/6 KV-CV

    3.6/6 (7.2) kV 90°C CROSS-LINKED POLYETHYLENE INSULATED AND PVC SHEATHED POWER CABLE


    Conductor   : Compact round stranded annealed copper,
    Single-core : Size 10 mm²  up to 1,000 mm²
    Multi-core : Size 10 mm²  up to 400 mm²
    Insulation : Cross-Linked polyethylene (XLPE)
    Core identification Single-core : Natural (Translucent)
    3 core : White, Red and Blue
    Shield : Copper tape
    Outer sheath : Black polyvinyl chloride (PVC/ST2)
    Classification : Maximum conductor temperature 90°C
    : Circuit voltage not exceeding 7,200 Volts
      Rated voltage (U0/U) 3.6/6 kV
      3,600 Volts between Line-to-Earth
      6,000 Volts between Line-to-Line
    Testing voltage : 12,500 Volts
    Reference standard : IEC 60502-1, IEC 60228, IEC 60332-1
  • 6/10 KV-CV

    6/10 (12) kV 90°C CROSS-LINKED POLYETHYLENE INSULATED AND PVC SHEATHED POWER CABLE


    Conductor   : Compact round stranded annealed copper,
    Single-core : Size 16 mm²  up to 1,000 mm²
    Multi-core : Size 16 mm²  up to 400 mm²
    Insulation : Cross-Linked polyethylene (XLPE)
    Core identification Single-core : Natural (Translucent)
    3 core : White, Red and Blue
    Shield : Copper tape
    Outer sheath : Black polyvinyl chloride (PVC/ST2)
    Classification : Maximum conductor temperature 90°C
    : Circuit voltage not exceeding 12,000 Volts
      Rated voltage (U0/U) 6/10 kV
      6,000 Volts between Line-to-Earth
      10,000 Volts between Line-to-Line
    Insulation shield layer : semi-conducting covering remove at splices or
      terminals
    Testing voltage : 21,000 Volts
    Reference standard : IEC 60502-1, IEC 60228, IEC 60332-1
  • 8.7/15 KV-CV

    8.7/15 (17.5) kV 90°C CROSS-LINKED POLYETHYLENE INSULATED AND PVC SHEATHED POWER CABLE


    Conductor   : Compact round stranded annealed copper,
    Single-core : Size 25 mm²  up to 1,000 mm²
    Multi-core : Size 25 mm²  up to 400 mm²
    Insulation : Cross-Linked polyethylene (XLPE)
    Core identification Single-core : Natural (Translucent)
    3 core : White, Red and Blue
    Shield : Copper tape
    Outer sheath : Black polyvinyl chloride (PVC/ST2)
    Classification : Maximum conductor temperature 90°C
    : Circuit voltage not exceeding 17,500 Volts
      Rated voltage (U0/U) 8.7/15 kV
      8,700 Volts between Line-to-Earth
      15,000 Volts between Line-to-Line
    Insulation shield layer : semi-conducting covering remove at splices or
      terminals
    Testing voltage : 30,500 Volts
    Reference standard : IEC 60502-1, IEC 60228, IEC 60332-1
  • 12/20 KV-CV

    12/20 (24) kV 90°C CROSS-LINKED POLYETHYLENE INSULATED AND PVC SHEATHED POWER CABLE


    Conductor   : Compact round stranded annealed copper,
    Single-core : Size 35 mm²  up to 1,000 mm²
    Multi-core : Size 35 mm²  up to 400 mm²
    Insulation : Cross-Linked polyethylene (XLPE)
    Core identification Single-core : Natural (Translucent)
    3 core : White, Red and Blue
    Shield : Copper tape
    Outer sheath : Black polyvinyl chloride (PVC/ST2)
    Classification : Maximum conductor temperature 90°C
    : Circuit voltage not exceeding 24,000 Volts
      Rated voltage (U0/U) 12/20 kV
      12,000 Volts between Line-to-Earth
      20,000 Volts between Line-to-Line
    Insulation shield layer : semi-conducting covering remove at splices or
      terminals
    Testing voltage : 42,000 Volts
    Reference standard : IEC 60502-1, IEC 60228, IEC 60332-1
  • 18/30 KV-CV

    18/30 (36) kV 90°C CROSS-LINKED POLYETHYLENE INSULATED AND PVC SHEATHED POWER CABLE


    Conductor   : Compact round stranded annealed copper,
    Single-core : Size 35 mm²  up to 1,000 mm²
    Multi-core : Size 35 mm²  up to 400 mm²
    Insulation : Cross-Linked polyethylene (XLPE)
    Core identification Single-core : Natural (Translucent)
    3 core : White, Red and Blue
    Shield : Copper tape
    Outer sheath : Black polyvinyl chloride (PVC/ST2)
    Classification : Maximum conductor temperature 90°C
    : Circuit voltage not exceeding 36,000 Volts
      Rated voltage (U0/U) 18/30 kV
      18,000 Volts between Line-to-Earth
      30,000 Volts between Line-to-Line
    Insulation shield layer : semi-conducting covering remove at splices or
      terminals
    Testing voltage : 63,000 Volts
    Reference standard : IEC 60502-1, IEC 60228, IEC 60332-1